Form
UTSEP/GPE GENERIC MONITORING FORM
Title
Mother kevin Namakupa P. School
Description
Inspection of Lightning Protection and other electrical Installation for GPE Schools
Inspector Name
bdkamu@gmail.com
Inspection Start time
Jan 11 2019 10:46 AM
Inspection End time
Jan 11 2019 11:20 AM


UTSEP/GPE GENERIC MONITORING FORM:

1. Location:

District:Mukono
County:Nakifuma
Sub-County:Ntunda
Parish:Ntunda
Village:Namukupa

2. Date of Visit:

Date of Visit:2019-01-11

3. Observations / Findings:

Observations / Findings:3 classroom Block. 1. A good resistance of 0.54Ohms was measured western side and 1.75ohms Eastern side of 3 classroom block. 2. Inspection chamber was constructed of only at western side and eastern side there's no inspection chamber. 3. Authentic materials were used. Administration Block. 1 A good resistance of 1.28Ohms is measured. 2. No inspection chamber 3. Main consumer unit was provided and installed. 4. Switch and socket provisions were neatly installed and provided with black covers 2 classroom Block 1. A resistance of 1.16ohms was measured on 2 classroom block 2. Socket and switch provisions were neatly installed and provided with black covers. 3. Consumer unit was installed 4. There's no inspection chamber provided

4. Recommendations:

Recommendations:1. Each down conductor must be provided with inspection chamber.

5. Record Location:

6. Evidence:

7. List of Persons Met:


Name::
Non

Title::
No

Gender::
AUTOMATIC

Tel. Contact::

8. Monitoring Officer:

Name:Kamugisha B.Didacus
Title:Electrical Engineering Ass. MOES
Status
Approved/Verified


Record Location


Photos of Evidence